Bepto on oma pühendumuses klientidele ja tipptasemel uuenduste pakkumisel teie kindel liitlane teie eesootaval teekonnal.
LZZBJ9-12/150b/2 & LZZBJ9-12/150b/4 Current Transformer 12kV Indoor CT: 5-1250A primary current, 0.2S/0.5/10P10/10P15/5P accuracy class, 150×In thermal capacity for 20-100A, 375×In dynamic current, 12/42/75kV insulation level, dual/quad winding, 10-30VA burden, 5A/1A secondary, 50/60Hz, GB1208 IEC60044-1.
Advanced LZZBJ9-12 Series Current Transformer: Indoor single-phase epoxy resin casting type CT conforming to GB1208 and IEC60044-1 standards, rated insulation level 12/42/75kV, rated frequency 50Hz or 60Hz, rated secondary current 5A or 1A, ambient temperature -5°C to +40°C, rated primary current range 5-1250A providing ultra-wide current coverage, flexible winding configurations including LZZBJ9-12/150b/2 (dual winding) and LZZBJ9-12/150b/4 (quad winding) enabling versatile metering and protection applications, flexible accuracy class combinations including 0.2S/10P, 0.5/10P, 0.2S/0.2/5P, and 0.5/5P10/10P20 with burden capacity 10-30VA, exceptional thermal performance with 150×In (1s thermal current) for 20-100A range ensuring superior short-circuit withstand capability, 375×In rated dynamic current providing maximum safety margin.
Superior Winding Flexibility and Exceptional Thermal Capacity: LZZBJ9-12 series features dual winding (/150b/2) and quad winding (/150b/4) configurations enabling diverse metering and protection requirements, exceptional 150 times rated current thermal capacity for low current range (20-100A) ensuring outstanding short-circuit protection, rated dynamic current up to 375×In for 20-100A range providing maximum safety margin, 1s thermal current 0.5-100kA covering comprehensive current applications from 5A to 1250A, suitable for 12kV switchgear, power distribution systems, substations, industrial power networks, energy management systems, and applications requiring flexible winding configurations with exceptional thermal withstand capability.
| LZZBJ9-12 Series Current Transformer Specifications | Parameeter | Üksus |
|---|---|---|
| Bränd | Bepto soojustussüsteemid | - |
| Mudeli number | LZZBJ9-12/150b/2 & LZZBJ9-12/150b/4 | - |
| Kategooria | Lülitusseadmed ja HV CT (kõrgepinge voolutrafo) | - |
| Toote tüüp | 12kV Indoor Single-Phase Epoxy Resin Casting Type Current Transformer with 5-1250A Range, 150×In Thermal Capacity, 375×In Dynamic Current, Dual Winding (/150b/2) and Quad Winding (/150b/4) Configurations, 0.2S/0.5/10P/5P Accuracy Class, 12/42/75kV Insulation for Metering & Protection | - |
| Põhitehnoloogia | Indoor Single-Phase Epoxy Resin Casting Type + 12kV Design + Exceptional 150×In Thermal Capacity for 20-100A Range + Superior 375×In Dynamic Current for 20-100A Range + Flexible Winding Configurations (Dual Winding /150b/2 and Quad Winding /150b/4) + GB1208 and IEC60044-1 Standards Compliant + Rated Insulation Level 12/42/75kV + Rated Frequency 50Hz or 60Hz + Rated Secondary Current 5A or 1A + Ambient Temperature -5°C to +40°C + Rated Primary Current Range 5-1250A + Ultra-Wide Current Coverage + Flexible Accuracy Classes (0.2S/10P, 0.5/10P, 0.2S/0.2/5P, 0.5/5P10/10P20) + Burden Capacity 10-30VA + 1s Thermal Current 0.5-100kA + Rated Dynamic Current 1.25-160kA + Versatile Metering and Protection Applications + Superior Short-Circuit Withstand Capability + Maximum Safety Margin | - |
| Võimsus (pinge) | 12kV | - |
| Nimipinge | 12kV | - |
| Hinnatud isolatsioonitase | 12/42/75 | kV |
| Nimisagedus | 50Hz või 60Hz | Hz |
| Nimivool sekundaarses voolusüsteemis | 5A või 1A | A |
| Nimivoolu vahemik | 5-1250 | A |
| Ümbritseva õhu temperatuur | -5°C kuni +40°C | °C |
| Struktuuri tüüp | Siseruumide ühefaasiline epoksüvaigu valutüüp | - |
| Mähise konfiguratsioon | Dual Winding (/150b/2) and Quad Winding (/150b/4) | - |
| Paigalduse tüüp | Siseruumides | - |
| Faas | Ühefaasiline | - |
| Standardite järgimine | GB1208 ja IEC60044-1 | - |
| FOB sadam | Ningbo/Shanghai | - |
| Maksetingimused | Western Union, T/T, Paypal | - |
| Epoksüvaigu valamine | Jah (ühefaasiline epoksüvaigu valamise tüüp siseruumides) | - |
| 12kV disain | Jah (12kV nimipinge) | - |
| 150×In soojusvõimsus | Jah (150 × soojusvool 20-100A vahemikus) | - |
| 375×In Dünaamiline voolutugevus | Jah (375×In dünaamiline vool 20-100A vahemikus) | - |
| Kahekordne mähise konfiguratsioon | Yes (/150b/2 Design with Two Windings) | - |
| Nelja mähise konfiguratsioon | Yes (/150b/4 Design with Four Windings) | - |
| Erakordne soojapidavus | Jah (Suurepärane lühise taluvus) | - |
| Maksimaalne ohutusvaru | Jah (375×In dünaamiline vool maksimaalse ohutuse tagamiseks) | - |
| 50Hz või 60Hz | Jah (nimisagedus 50Hz või 60Hz) | - |
| 12kV nimipinge | Jah (nimipinge 12kV) | - |
| GB1208 nõuetele vastav | Jah (vastavalt standardile GB1208) | - |
| IEC60044-1 nõuetele vastav | Jah (kooskõlas standardiga IEC60044-1) | - |
| 12/42/75kV isolatsioon | Jah (Nimeline isolatsioonitase 12/42/75kV) | - |
| 5A või 1A Teisene | Jah (nimivool 5A või 1A) | - |
| -5°C kuni +40°C Keskkond | Jah (keskkonnatemperatuur -5°C kuni +40°C) | - |
| 5-1250A Esmane vahemik | Jah (nimivoolu vahemik 5-1250A) | - |
| Ülilaiune voolu katvus | Jah (alates 5A kuni 1250A primaarvool) | - |
| 0,2S Täpsusklass | Jah (0,2S mõõtetäpsuse klass saadaval) | - |
| 0,2 Täpsusklass | Jah (0,2 mõõtetäpsuse klass saadaval) | - |
| 0,5 Täpsusklass | Jah (0,5 mõõtetäpsuse klass saadaval) | - |
| 10P10 Kaitseklass | Jah (10P10 kaitse täpsusklass saadaval) | - |
| 10P15 Kaitseklass | Jah (10P15 kaitse täpsusklass saadaval) | - |
| 5P10 Kaitseklass | Jah (5P10 kaitse täpsusklass saadaval) | - |
| 5P20 Kaitseklass | Jah (5P20 kaitse täpsusklass saadaval) | - |
| 10-30VA koormuse võimsus | Jah (koormuse võimsus 10-30VA) | - |
| LZZBJ9-12/150b/2 | ||||||
| Nimeline primaarvool (A) | Täpsusklasside kombinatsioon | 0,2S (VA) | 0.2 (0.5) (VA) | 10P (VA) | 1s soojusvool (kA) | Dünaamiline nimivool (kA) |
| 5 | 0,2S / 10P10 | – | 10 | 15*, 20 | 0.5 | 1.25 |
| 10 | 0,2S / 10P15 | – | 10 | 15*, 20 | 1 | 2.5 |
| 15 | 0.2 / 10P10 | – | 10 | 15*, 20 | 1.5 | 3.75 |
| 20 | 0.2 / 10P15 | – | 10 | 15*, 20 | 3 | 7.5 |
| 25 | 0.5 / 10P10 | – | 10 | 15*, 20 | 3.75 | 9.3 |
| 30 | 0.5 / 10P15 | – | 10 | 15*, 20 | 4.5 | 11.2 |
| 40 | 0.5 / 10P15 | – | 10 | 15*, 20 | 6 | 15 |
| 50 | 0.5 / 10P15 | – | 10 | 15*, 20 | 7.5 | 18.7 |
| 75 | 0.5 / 10P15 | – | 10 | 15*, 20 | 10 | 25 |
| 100 | 0.5 / 10P15 | 10 | – | – | 15 | 37.5 |
| 150 | 0.5 / 10P15 | 10 | – | – | 22.5 | 56 |
| 200 | 0.5 / 10P15 | 10 | – | – | 31.5 | 80 |
| 300 | 0.5 / 10P15 | – | 10*, 15 | – | 45 | 112.5 |
| 400 | 0.5 / 10P15 | – | 10*, 15 | – | 63 | 130 |
| 500 | 0.5 / 10P15 | – | 10*, 15 | – | 63 | 130 |
| 600 | 0.5 / 10P15 | – | 15*, 30 | – | 80 | 110 |
| 800 | 0.5 / 10P15 | – | 15*, 30 | – | 80 | 110 |
| 1000 | 0.5 / 10P15 | – | 15*, 30 | – | 80 | 110 |
| 1200 | 0.5 / 10P15 | – | 15*, 30 | – | 100 | 160 |
|
Märkus Values marked with * apply to class combinations 0.2 / 5P10 / 10P15 and 0.5 / 5P10 / 10P20. |
||||||
| LZZBJ9-12/150b/2 | |||||||||
| Nimeline primaarvool (A) | Täpsusklasside kombinatsioon | 0,2S (VA) | 0,2 (VA) | 0,5 (VA) | (5)10P10 (VA) | (5)10P15 (VA) | (5)10P20 (VA) | 1s soojusvool (kA) | Dünaamiline nimivool (kA) |
| 20–100 | 0,2(S)/10P 0.5/10P |
– | 10 | 10 | 10*, 30 | 15*, 20 | 15*, 10 | 150 × In | 375 × In |
| 150, 200 | 0,2(S)/10P 0.5/10P |
– | 10 | 10 | 10*, 30 | 15*, 20 | 15*, 10 | 31.5 | 80 |
| 300, 400 | 0.2(S)/0.2/5P 0.2(S)/0.5/5P |
10 | – | – | – | – | 15 | 45 | 112.5 |
| 500 | 0.2(S)/0.5/5P20 | 10 | 10 | 15 | 15*, 30 | 20 | 15 | 63 | 130 |
| 600–800 | 0.2(S)/5P10/10P15 0.5/5P10/10P20 |
– | – | – | – | 15*, 20 | – | 63 | 130 |
| 1000–1250 | 0.5/5P10/10P20 | – | 15 | 20 | – | 15*, 20 | – | 80 | 160 |
|
Märkus Values marked with * apply to class combinations 0.2 / 5P10 / 10P15 and 0.5 / 5P10 / 10P20. |
|||||||||
| Nimivool (A) | 150×In Soojusvool (kA) | 375×In Dünaamiline vool (kA) |
|---|---|---|
| 20 | 3 | 7.5 |
| 30 | 4.5 | 11.25 |
| 40 | 6 | 15 |
| 50 | 7.5 | 18.75 |
| 60 | 9 | 22.5 |
| 75 | 11.25 | 28.125 |
| 80 | 12 | 30 |
| 100 | 15 | 37.5 |
| Mudel | Mähise konfiguratsioon | Tüüpilised täpsusklassid | Peamine eelis | Tüüpilised rakendused |
|---|---|---|---|---|
| LZZBJ9-12/150b/2 | Kahekordne mähis (kaks mähist) | 0.2S/10P, 0.5/10P, 0.2/10P | Simple metering + protection configuration | Standard metering and single protection relay applications (5-1200A) |
| LZZBJ9-12/150b/4 | Quad Winding (neli mähist) | 0.2(S)/10P, 0.5/10P, 0.2(S)/0.2/5P, 0.5/5P10/10P20 | Advanced metering + multiple protection configuration | High-precision metering and multiple protection relay applications (20-1250A) |
| LZZBJ9-12/150b/2 | |||
| Täpsusklasside kombinatsioon | Mähkimisfunktsioon | Rakendusstsenaarium | Tüüpiline vooluväli |
| 0,2S/10P10 | Suure täpsusega mõõtmine + standardne kaitse | Täpne arveldamine ja releekaitse | 5-10A |
| 0,2S/10P15 | Suure täpsusega mõõtmine + täiustatud kaitse | Precise billing and enhanced relay protection | 10A |
| 0.2/10P10 | Suure täpsusega mõõtmine + standardne kaitse | Täpne mõõtmine ja releekaitse | 15A |
| 0.2/10P15 | Suure täpsusega mõõtmine + täiustatud kaitse | Accurate metering and enhanced relay protection | 20A |
| 0.5/10P10 | Standardne mõõtmine + standardne kaitse | Üldine mõõtmine ja releekaitse | 25A |
| 0.5/10P15 | Standardne mõõtmine + tõhustatud kaitse | General metering and enhanced relay protection | 30-1200A |
| LZZBJ9-12/150b/4 | |||
| Täpsusklasside kombinatsioon | Mähkimisfunktsioon | Rakendusstsenaarium | Tüüpiline vooluväli |
| 0,2(S)/10P | High-precision metering + protection (multiple windings) | Precise billing and multiple relay protection | 20-200A |
| 0.5/10P | Standard metering + protection (multiple windings) | General metering and multiple relay protection | 20-200A |
| 0.2(S)/0.2/5P | Dual high-precision metering + 5P protection | Dual precise billing and 5P relay protection | 300-400A |
| 0.2(S)/0.5/5P | High-precision + standard metering + 5P protection | Mixed metering requirements and 5P relay protection | 300-400A |
| 0.2(S)/0.5/5P20 | High-precision + standard metering + 5P20 protection | Mixed metering and enhanced 5P20 relay protection | 500A |
| 0.2(S)/5P10/10P15 | High-precision metering + 5P10 + 10P15 protection | Precise billing and dual protection relay | 600-800A |
| 0.5/5P10/10P20 | Standard metering + 5P10 + 10P20 protection | General metering and dual protection relay | 600-1250A |
| Esmane voolu vahemik | Soojusvool (kA) | Dünaamiline vool (kA) | Mudel | Taotlus |
|---|---|---|---|---|
| 5-10A | 0.5-1 | 1.25-2.5 | /150b/2 | Very low current with dual winding |
| 15-75A | 1.5-10 | 3.75-25 | /150b/2 | Low current with dual winding |
| 20-100A | 150×In (3-15kA) | 375×In (7,5-37,5kA) | /150b/4 | Madala keskmise vooluga, erakordse termilise kaitsega ja neljakordne mähis |
| 100-200A | 15-31.5 | 37.5-80 | /150b/2 & /150b/4 | Medium current with dual or quad winding |
| 300-500A | 45-63 | 112.5-130 | /150b/2 & /150b/4 | Medium-high current with dual or quad winding |
| 600-1000A | 63-80 | 110-130 | /150b/2 & /150b/4 | High current with dual or quad winding |
| 1000-1250A | 80-100 | 110-160 | /150b/2 & /150b/4 | Very high current with dual or quad winding |
Bepto on juhtiv Hiina elektriisolatsiooniettevõte, mis keskendub tulevaste elektrisüsteemide jaoks täiustatud lahenduste väljatöötamisele. Me toetame ülekande- ja jaotussüsteemide ohutust ja kasvu, kusjuures meie pikaajaliste partnerite hulka kuuluvad State Grid, ABB, Schneider, Siemens ja GE. Meie teenused jõuavad klientideni enam kui 22 riigis.
Bepto keskendub maailmaturule ja pakub oma klientidele kohalikule turule sobivaid tooteid:
Bepto on oma pühendumuses klientidele ja tipptasemel uuenduste pakkumisel teie kindel liitlane teie eesootaval teekonnal.