Unwavering in our dedication to customers and delivering cutting-edge innovations,Bepto stands as your steadfast ally on the journey ahead.
IACM-50A Overhead Switch Disconnector: 12-36kV 1250A air-break tree network LBS, end-of-line isolation, substation cluster, NF C 64-140 Type I, 2000m altitude, -30°C to +40°C.
Advanced IACM-50A Overhead Switch Disconnector Series: Premium IACM-12~36/400-50A overhead switch designed for end-of-line placement in tree-like HVA network structures, isolating substation clusters for downstream line work, compliant with NF C 64-140 Type I standard (01/1990), featuring air-break technology with isolation gate knife and arc rod for rapid energy storage movement, arc lengthening and air cooling extinguishment, delivering 200-1250A rated current with 50A active load breaking, 2.5A no-load transformer breaking, 10A no-load line breaking capacity, 12.5kA (1s) short-time withstand, 31.5kA peak withstand, 2000 mechanical cycles, suitable for radial/ring network lines, transformer circuits with HV current limiting fuses.
Tree Network and Substation Cluster Ready: IACM-50A incorporates simple structure, less maintenance, strong arc extinguishing ability, high insulation level break, high reliability for tree-like network end-of-line applications, operating at -30°C to +40°C, altitudes ≤2000m, Grade IV air pollution, earthquake intensity ≤8, providing reliable air-break overhead switching solution for HVA tree network substation cluster isolation and downstream line work.
| IACM-50A Overhead Switch Disconnector Specifications | 12kV | 17.5kV | 24kV | 36kV | Unit |
|---|---|---|---|---|---|
| Model Number | IACM-12/400-50A | IACM-17.5/400-50A | IACM-24/400-50A | IACM-36/400-50A | – |
| Alternative Model | ISAR-S-12 | ISAR-S-17.5 | ISAR-S-24 | ISAR-S-36 | – |
| Brand | Bepto Insulation Systems | Bepto Insulation Systems | Bepto Insulation Systems | Bepto Insulation Systems | – |
| Product Type | Air-Break Overhead Switch Disconnector (Load-Break Switch) | Air-Break Overhead Switch Disconnector (Load-Break Switch) | Air-Break Overhead Switch Disconnector (Load-Break Switch) | Air-Break Overhead Switch Disconnector (Load-Break Switch) | – |
| Application Focus | End-of-Line in Tree Network, Substation Cluster Isolation | End-of-Line in Tree Network, Substation Cluster Isolation | End-of-Line in Tree Network, Substation Cluster Isolation | End-of-Line in Tree Network, Substation Cluster Isolation | – |
| Standard Compliance | NF C 64-140 Type I (01/1990) | NF C 64-140 Type I (01/1990) | NF C 64-140 Type I (01/1990) | NF C 64-140 Type I (01/1990) | – |
| Rated Voltage | 12 | 17.5 | 24 | 36 | kV |
| Rated Current | 200/400/630/1250 | 200/400/630/1250 | 200/400/630/1250 | 200/400/630/1250 | A |
| Rated Active Load Breaking Current | 50 | 50 | 50 | 50 | A |
| Rated No-Load Transformer Breaking Current | 2.5 | 2.5 | 2.5 | 2.5 | A |
| Rated No-Load Line Breaking Capacity | 10 | 10 | 10 | 10 | A |
| 1min Power Frequency Withstand (Phase/Earth) | 42 | 45 | 55 | 95 | kV |
| Power Frequency Withstand (Open Contacts) | 48 | 55 | 69 | 105 | kV |
| Lightning Impulse Withstand (Phase/Earth) | 75 | 95 | 125 | 170 | kV |
| Lightning Impulse Withstand (Open Contacts) | 85 | 105 | 145 | 195 | kV |
| Rated Short-Time Withstand Current | 12.5 | 12.5 | 12.5 | 12.5 | kA |
| Rated Short-Circuit Duration | 1 | 1 | 1 | 1 | s |
| Rated Peak Withstand Current | 31.5 | 31.5 | 31.5 | 31.5 | kA |
| Mechanical Life | 2000 | 2000 | 2000 | 2000 | cycles |
| Manual Operating Torque | ≤200 | ≤200 | ≤200 | ≤200 | Nm |
| Contact Opening Distance | >500 | >600 | >800 | >1030 | mm |
| Contact Pressure | 200 | 200 | 200 | 200 | N |
| Main Loop Resistance | ≤150 | ≤150 | ≤150 | ≤150 | μΩ |
| Ambient Temperature | -30 to +40 | -30 to +40 | -30 to +40 | -30 to +40 | °C |
| Daily Temperature Difference | ≤32 | ≤32 | ≤32 | ≤32 | K |
| Altitude | ≤2000 | ≤2000 | ≤2000 | ≤2000 | m |
| Air Pollution Level | Grade IV (GB5585) | Grade IV (GB5585) | Grade IV (GB5585) | Grade IV (GB5585) | – |
| Max Wind Pressure | ≤700 | ≤700 | ≤700 | ≤700 | MPa |
| Earthquake Intensity | ≤8 | ≤8 | ≤8 | ≤8 | – |
| Ice Thickness | ≤10 | ≤10 | ≤10 | ≤10 | mm |
| IEC Standards | IEC60265-1, IEC62271-1, IEC62271-103 | IEC60265-1, IEC62271-1, IEC62271-103 | IEC60265-1, IEC62271-1, IEC62271-103 | IEC60265-1, IEC62271-1, IEC62271-103 | – |
| Application | End-of-Line in Tree-Like HVA Network, Substation Cluster Isolation, Downstream Line Work, Radial/Ring Network, Transformer Circuits with HV Fuses | End-of-Line in Tree-Like HVA Network, Substation Cluster Isolation, Downstream Line Work, Radial/Ring Network, Transformer Circuits with HV Fuses | End-of-Line in Tree-Like HVA Network, Substation Cluster Isolation, Downstream Line Work, Radial/Ring Network, Transformer Circuits with HV Fuses | End-of-Line in Tree-Like HVA Network, Substation Cluster Isolation, Downstream Line Work, Radial/Ring Network, Transformer Circuits with HV Fuses | – |
Bepto is a leading Chinese company in electrical insulation, focused on developing advanced solutions for future power systems. We support transmission and distribution safety and growth, with long-term partners including State Grid, ABB, Schneider, Siemens, and GE. Our services reach clients in over 22 countries.
Bepto focuses on the global market and provides our clients with products suitable for the local market:
Unwavering in our dedication to customers and delivering cutting-edge innovations,Bepto stands as your steadfast ally on the journey ahead.