24kV Earthing Switch

Fast-ActingEarthingSwitches

Engineered for absolute personnel safety. Our Medium Voltage Grounding Switches feature robust spring-loaded mechanisms that guarantee flawless short-circuit making capacity during critical maintenance operations.

JN15-12 Indoor HV Earthing Switch
IEC 62271-102 Compliant

UV-Resistant Shield

1 dari 1

Earthing Switch Tags

Product Category

JN15-12 Indoor HV Earthing Switch 12kV 630A 31.5kA - Switchgear Grounding Protection 42kV Power Frequency 75kV Lightning Impulse 80kA Making Current

JN15 Indoor AC HV Earthing Switch 12-40.5kV 31.5kA – Short-Circuit Making Capacity 80kA 65kV Power Frequency 125kV Lightning Impulse Resin Insulator

What is an Earthing Switch?

An Earthing Switch (Grounding Switch) is a critical safety device used to mechanically connect a de-energized electrical circuit to ground. Its primary purpose is to discharge residual static electricity from cables and busbars, ensuring a safe, zero-voltage environment for maintenance personnel.

The "Make-Proof" Requirement

Modern networks require Fast-Acting Earthing Switches. If an operator accidentally closes the earthing switch onto a live line, a massive short-circuit occurs. Fast-acting switches use a charged spring mechanism to force the contacts closed in milliseconds. This prevents an open-air arc explosion, successfully making the short circuit and surviving long enough for the upstream circuit breaker to trip.

ENGINEERING PRECISION

The Anatomy of a Fast-Acting Switch

Stored-Energy Spring Mechanism

The closing speed is entirely independent of the operator. Turning the handle compresses a powerful internal spring. Once passed the dead-center point, the spring violently releases, driving the grounding blades into the contacts at extreme velocity to secure a solid connection before an arc can melt the copper.

Live-Line Indicators (Sensors)

We offer models with built-in capacitive voltage sensors housed within the epoxy resin post insulators. These connect directly to the switchgear's Live-Line Indicator (DXN series), warning operators visually if the busbar is still energized prior to earthing.

Electromagnetic Blocking

Equipped with an electromagnetic locking coil (DSN). If voltage is detected on the line, the coil actively locks the operating shaft, making it physically impossible for the operator to insert the handle and close the earthing switch, strictly adhering to the "Five Preventions" safety protocol.

SEAMLESS ASSEMBLY

Designed for Panel Builders

Our JN15 and JN22 series earthing switches are globally recognized as the standard for medium voltage metal-clad switchgear.

Customizable Phase Distance

Available in 150mm, 210mm, 275mm, and custom phase distances to perfectly align with your cable compartment layouts, accommodating cabinet widths from 650mm up to 1000mm.

Door Interlock Linkage

Supplied with the necessary mechanical linkage arms. The switchgear's rear cable compartment door can only be unlocked and opened when the earthing switch is securely in the "Closed/Grounded" position.

Flexible Mounting Angles

The base chassis allows for horizontal or vertical mounting depending on the busbar drop, maximizing space efficiency inside the switchgear.

Technical Specification Matrix

Standard ratings for Indoor Fast-Acting Earthing Switches (JN15 / JN22 Series).
Parameter Unit 12kV Series (JN15) 24kV Series (JN15) 36kV Series (JN22)
Rated Voltage kV 12 24 40.5
Rated Short-Time Withstand Current (3s) kA 31.5 / 40 / 50 25 / 31.5 25 / 31.5
Rated Short-Circuit Making Current (Peak) kA 80 / 100 / 130 63 / 80 63 / 80
Lightning Impulse (BIL) - To Earth kV 75 125 185
Phase-to-Phase Distance Options mm 150 / 210 / 250 210 / 275 300 / 400
Mechanical Endurance Ops 2,000 to 5,000 Operations (Maintenance Free)
Optional Live-Line Sensor - Available (Capacitive dividers cast into insulators)
Crucial Sizing Note: The Short-Circuit Making Current of the earthing switch must always be equal to or greater than the peak withstand current of the main circuit breaker protecting that line.
Industry Resources

Technical Insights for Panel Builders

KNOWLEDGE BASE

Selection FAQ

JN15 is our standard, highly compact series optimized for 12kV and 24kV applications. JN22 features a heavier, reinforced frame and larger insulators, specifically engineered to handle the higher insulation requirements and massive mechanical forces encountered in 36kV and 40.5kV systems.

Yes. Because switchgear cabinet depths vary, we supply the earthing switch with customizable hexagon operating shafts. They can be extended to reach the front operating panel of deep cabinets or configured for side-wall operation, depending on your cabinet layout.

Yes, all our earthing switches are supplied with heavy-duty tinned copper braided straps. These braids reliably conduct the fault current from the moving blade shaft to the grounded base frame, ensuring the current safely bypasses the mechanical bearings to prevent welding during a short circuit.

OEM Project Pricing

Secure the highest quality safety components for your switchgear manufacturing. Provide your parameters for rapid dimensioning, 3D step models, and volume pricing.
CUSTOMIZABLE

Phase Distances & Shaft Lengths

TESTED & CERTIFIED

Full IEC Type Test Reports

24-Hour Rapid Response

Submit your requirements on a business day, and our engineers will provide an initial OEM proposal within 24 hours.

Form Contact
🔒 Your information is secure and encrypted.
Bepto Catalog

Get Free Product Catalog & Technical Datasheets

We supply complete medium & high voltage solutions, including:

• Air Insulation Series
• Gas Insulation Series
• Switching Devices
• Instrument Transformers

Catalog Pop
🔒 Your information is secure and encrypted.