Engineered for KYN28 switchgear compartments. Featuring internal shielding screens for optimal electric field control and superior bending strength up to 12.5kN.
A conductive screen equalizes potential distribution.
Prevents corona and breakdown at the flange interface.
Rated from 4kN up to 12.5kN bending load.
Void-free epoxy resin ensures structural integrity under stress.
| Characteristics | Unit | 12kV Series | 24kV Series | 40.5kV Series |
|---|---|---|---|---|
| Rated Voltage | kV | 12 | 24 | 40.5 |
| PF Withstand Voltage (1min) | kV | 42 | 65 | 95 |
| Lightning Impulse (BIL) | kV | 75 | 125 | 185 |
| Bending Failure Load | kN | 4 / 8 / 12.5 | 4 / 8 / 12.5 | 4 / 8 |
| Rated Current | A | 630-4000 | 630-3150 | 1250-2500 |
We have molds for standard busbar sizes (e.g., 60x10, 80x10, 100x10, 120x10). For non-standard sizes, we can customize the aperture window.
Yes, the bushing comes pre-assembled with a metal mounting plate (Steel or Aluminum) with grounding terminals.
For rated currents >1500A, we strongly recommend Aluminum (non-magnetic) plates to prevent eddy current heating. Below 1500A, Steel is sufficient and cost-effective.
Don’t see your busbar size? Our engineering team provides free CAD modification services.
Latest industry news and maintenance guides for insulation components.
We supply complete medium & high voltage solutions, including:
• Air Insulation Series
• Gas Insulation Series
• Switching Devices
• Instrument Transformers